Description
The Notifier RP-2001E Deluge-Preaction Control Panel is a six-zone, microprocessor-based fire alarm control unit designed for single and dual-hazard water-based suppression systems. Equipped with an FLPS-7 power supply rated at 240 VAC, 50 Hz, 2.085 amps, this panel provides precise detection and control for deluge and preaction fire suppression applications.
Technical Specifications
| Condition |
New/Never Used Surplus |
| Brand |
Notifier |
| Category |
Fire Alarm Equipment |
| Part Number |
RP-2001E |
| Subcategory |
Deluge-Preaction Control Panel |
| System Type |
Six-zone fire alarm and releasing control panel |
| Supported Hazards |
Single or dual hazard (deluge/preaction) |
| Power Supply |
FLPS-7 integrated power supply |
| Input Voltage |
240 VAC, 50 Hz |
| Input Current |
2.085 A |
| Output Voltage |
24 VDC nominal |
| Detection Zones |
Six supervised zones |
| Notification Circuits |
Two supervised outputs (NACs) |
| Relay Outputs |
Programmable relays for alarm and trouble functions |
| Communication Interface |
Notifier-compatible modules and accessories |
| Circuit Supervision |
Open, short, and ground fault detection |
| Operating Temperature Range |
32°F to 120°F (0°C to 49°C) |
| Humidity Range |
Up to 93% RH, non-condensing |
| Cabinet Material |
Steel enclosure, red powder coat |
| Compliance |
UL Listed; NFPA 72 and releasing service compliant |
| Dimensions |
Approx. 26" H × 18" W × 5.5" D |
| Weight |
29 lb (13.15 kg) |
Information About RP-2001E
The RP-2001E is a Notifier six-zone control panel engineered to manage deluge and preaction sprinkler systems in industrial, commercial, and special hazard facilities. It supports both single and dual-hazard configurations, offering flexibility for complex fire protection layouts. The integrated FLPS-7 power supply provides stable 24 VDC system power and supervision for connected detection and release circuits. Designed for compatibility with Notifier detectors, modules, and notification appliances, the RP-2001E meets UL and NFPA requirements for releasing service and fire suppression control.
Key Features:
- Six Detection Zones: Supports multiple supervised input circuits for system flexibility.
- Dual-Hazard Capability: Configurable for single or dual-hazard deluge or preaction systems.
- Integrated Power Supply: Includes FLPS-7 module rated at 240 VAC, 50 Hz, 2.085 A.
- Releasing Service Approved: Designed and listed for use with deluge and preaction suppression applications.
- Notifier System Integration: Compatible with a wide range of Notifier detectors and notification devices.
- Supervised Circuits: Ensures fault detection for open, short, and ground conditions.
- User-Friendly Interface: LED indicators and zone controls simplify monitoring and operation.
- UL and NFPA Compliant: Meets requirements for fire alarm and releasing service panels.
The RP-2001E delivers the reliability and precision required for deluge and preaction fire suppression control in demanding industrial and commercial applications.